Home / Insights / Safety & protection

Safety & protection3 min readLast updated September 2026

Pressure cascades in containment: pascals, not cubic metres

A room is deemed critical – so it gets more exhaust air. This reflex is expensive and offers no protection: hazardous substances stay in the room because a stable pressure differential dictates the direction of flow, not because a lot of air is moved.

Key points

  • Containment is created by a directed pressure differential between rooms – airflow is merely the means of establishing it.
  • The pressure step results from the offset between supply and exhaust air; how large it must be is determined primarily by the airtightness of the room envelope.
  • The direction follows the protection objective: personnel and environmental protection require negative pressure, product protection positive pressure – where both meet, an airlock belongs in between.
  • A cascade is only safe once it demonstrably holds even with the door open, at part load and over years.

01The fallacy: critical room, more exhaust air

In laboratories, radionuclide areas and biosafety zones, the same reflex appears early on: a room is “critical”, so it gets more exhaust air. More air feels like more safety. Technically, however, it offers no protection. A room can be operated with a high air change rate and still lose containment – if supply and exhaust air are equal or the offset has the wrong sign.

02The principle: a staircase of room pressures

A pressure cascade is a sequence of room pressures along a route, for example corridor – airlock – laboratory. Each step amounts to only a few pascals, but clearly determines the direction in which air flows through door gaps and penetrations. What matters is not the absolute value, but that the direction is correct along the entire route. Swiss radiological protection legislation puts it exactly this way: the pressure in rooms with a greater risk of contamination must be lower than in rooms with a lesser risk.

The direction follows from the protection objective. If the hazard is to remain in the room – radioactive, biological or chemical substances – the room is kept at negative pressure. If contamination is to remain outside, for example in aseptic manufacturing, it is kept at positive pressure. Where both logics meet, an airlock with its own pressure regime belongs in between.

Principle of the pressure cascade: for personnel protection, pressure falls from the corridor via the airlock to the laboratory; for product protection, it rises towards the cleanroom; air always flows from higher to lower pressurePEOPLE & ENVIRONMENT · NEGATIVE PRESSURE0 Pa0 PaCorridor−10 PaAirlock−20 PaLaboratoryAir flows towards the hazard – which stays in the room.PRODUCT PROTECTION · POSITIVE PRESSURE0 Pa0 PaCorridor+10 PaAirlock+20 PaCleanroomAir flows away from the cleanroom – germs stay outside.Assumed pressure values for illustration · arrows: airflow through door gaps, always from higher to lower pressure
Two protection objectives, two directions Schematic with assumed pressure values

03The lever is airtightness, not airflow

The pressure step results from the offset between supply and exhaust air. It must be as large as the air that escapes through the leaks in the envelope at the desired pressure differential. This leakage increases only roughly with the square root of the pressure differential, but directly with the leakage area: a fourfold pressure step costs roughly twice the offset air, half the leakage area saves half.

Fictitious calculation example: transfer air increases with the square root of the pressure difference; with 100 square centimetres of leakage, approx. 110 cubic metres per hour for 15 pascals and 220 for 60 pascals; with half the leakage area, half as muchTRANSFER AIR FOR ONE PRESSURE STEP · FICTITIOUS CALCULATION EXAMPLE050100150200250015304560Pressure difference in Pam³/h100 cm² leakage area50 cm² – twice as airtight≈ 110≈ 220≈ 55Transfer air fora 4-fold pressure step½Transfer air withhalf the leakage areaAssumed: Q ≈ Cd · A · √(2 ΔP / ρ) with Cd = 0.6 and ρ = 1.2 kg/m³ · no substitute for design
Airtightness beats airflow Fictitious calculation example with assumed values, simplified orifice equation

≈ 110 m³/hoffset air for 15 Pa negative pressure with an assumed effective leakage area of 100 cm²

The large airflows of a laboratory stem from heat and substance loads, not from containment. Anyone who cannot hold the pressure step therefore usually has an airtightness or control problem – not an airflow problem.

04Where cascades fail in operation

  • Door opening causes the pressure step to collapse abruptly – airlocks with mutually interlocked doors absorb this.
  • Variable air volume fume cupboards change the exhaust air within seconds; the supply air must follow quickly enough.
  • Filter loading shifts the fan curve; without pressure control, the cascade drifts.
  • Retrofitted penetrations for cables and pipes increase the leakage area.
  • Part load and night-time operation: the direction must be maintained even at reduced airflow.

05What this means for your project

Require a pressure step plan at an early stage, with pressure differential, direction and airlock concept for each room – it is the actual control document, not the airflow table. Specify the airtightness of the envelope as a testable value, have the offset documented for each room, and have the pressure differentials at the relevant doors monitored and alarmed. Accept the cascade in two stages: first with the doors closed, then under defined door-open scenarios.

And not every sensitive room is a pressurised room: for electron microscopes, for example, vibration, stray fields and temperature stability are what count – a sharp cascade would only bring draughts there.

Takeaway

A pressure cascade contains hazardous substances with pascals, not with cubic metres – and the most economical way to get there is an airtight envelope with a cleanly controlled offset.

Standards and sources

  • DIN 1946-7:2022-08 – Ventilation and air conditioning, Part 7: Ventilation systems in laboratories
  • EN 14175 – Fume cupboards
  • SIA 382/1 – Ventilation and air-conditioning systems, general principles and requirements
  • FDHA Ordinance on the Handling of Radioactive Material (UraM, SR 814.554), Art. 15
  • Containment Ordinance (ContainO, SR 814.912), Annex 4
  • EU GMP Guide, Annex 1 “Manufacture of Sterile Medicinal Products” (2022), points 4.14–4.16

SEDC AG · Article from our internal training series “Technik Praxis”, abridged for clients and users.

Full version & expert discussion

More depth for your project.

The full version contains the derivation of the leakage and offset calculation, guide values for pressure steps by room type, the control concept for door opening and variable air volume fume cupboards, and our checklist for specification and acceptance of the cascade. We are happy to go through it with you – applied to your installation.

Request an expert discussion